How to read electrical schematics: a guide for maintenance technicians

Hundreds of pages, one sensor that won't switch. How to read a machine's electrical drawings: symbols, device tags, page references, wire colors and PLC pages.

The HMI says the infeed sensor -B12 isn’t switching. The drawing set for the machine runs to a few hundred pages, the sensor is on one of them, and the cabinet in front of you holds a couple of hundred terminals. If you know how the pages point at each other, finding the right wire takes minutes. If you don’t, it can take the rest of the shift.

An electrical schematic shows how a machine’s electrical parts are connected, drawn as symbols laid out by how the circuit works, not by where the parts sit in the cabinet. Reading one comes down to three things: knowing the symbols and device tags, following the page and column references from one page to the next, and remembering that contacts are drawn at rest, so you have to work out which relays are actually energized. With that, you can follow a signal from a PLC input through the terminal strip to the sensor in the field.

What an electrical schematic is

There are two drawings you’ll use most. A schematic is laid out to show how the system works, while a wiring diagram places the equipment and wiring roughly where they really are (DOE). A machine’s documentation set usually has a few more:

  • Schematic (circuit or elementary diagram): how each circuit works, for tracing it.
  • Interconnection or wiring diagram: which wire runs between which terminals and devices.
  • Terminal diagram: every terminal on a strip, with the wires on both sides.
  • Cable diagram: each cable, its cores and where both ends go.
  • Panel layout: where each device sits in the cabinet.

In the US, NFPA 79 requires schematic diagrams to be supplied with a machine’s electrical equipment. US control schematics are usually drawn as a ladder: control power on the left rail, the coil common on the right, and devices on horizontal rungs between them (Los Alamos National Laboratory drawing standard). Internationally, IEC 61082-1 sets the rules (IEC), and European machine documentation is often drawn in EPLAN, which this guide uses for its examples.

The parts of a machine schematic

  • The title block, usually in the bottom right corner, with everything that identifies the drawing. Check the revision against your plant’s current issue. Numbering varies by builder, and a change made on site may be marked by hand on the cabinet copy or missing from the drawing altogether. Often the only record of it is the technician who made it, which is a textbook case of tribal knowledge. So compare the drawing with the wiring.
  • A sheet index listing the pages by function.
  • Power distribution: the main disconnect, fuses or breakers, transformers and the 24 V DC supply.
  • Power circuits: motors, drives and heaters with their contactors and protection.
  • Control circuits: relays, safety circuits, push buttons and pilot lights.
  • PLC pages: each input and output card with the device on each channel.
  • Terminal and cable diagrams and a parts list, which EPLAN generates from the schematic data (EPLAN).

Electrical schematic symbols

There are two families of symbols. European machines use IEC 60617, by now a database of more than 1,500 symbols (IEC). US machines use IEEE 315, which NFPA 79 still refers to although IEEE has listed it as inactive since 2019 (IEEE), and some older ones carry JIC symbols. The same relay looks quite different in each:

The same relay in US and IEC symbols, drawn with the coil off

US, IEEE 315

IEC 60617

State

Relay coil

US CR1
IEC -K1 A1 A2

Off Energized

Normally open contact

US CR1
IEC -K1 13 14

Open Closed

Normally closed contact

US CR1
IEC -K1 21 22

Closed Open

  • Conducts
  • No current

This is how both drawings show the relay: coil off. The normally open contact is open, and the normally closed contact is closed.

The drawing stays the same. On the machine, the energized coil has closed the normally open contact and opened the normally closed one.

Simplified after IEEE 315 and IEC 60617, with both drawn left to right. Tags after NFPA 79 (CR, control relay) and IEC 81346-2 (K); contact numbers after IEC 60947-1.

Every drawing set should have a symbol legend. On a machine you don’t know, read it first. It takes five minutes and saves you from the builder’s private habits.

One rule holds in both families: relays and contacts are drawn de-energized, in what’s sometimes called the shelf state. A normally open contact is drawn open even when, on the running machine, its relay is pulled in and the contact is closed. Reading a schematic means working out which coils are energized, and so which contacts have changed state. US drawings mark the exception with separate limit switch symbols, held open and held closed, for a switch the machine keeps pressed at rest.

Device tags: what -K3, =A1 and +CAB1 mean

Each device has a tag that identifies it on every page and on the device itself in the cabinet (IEC 81346-1). On a European drawing a full tag can have three parts, each with its own prefix:

  • = function: which part of the machine it belongs to, for example =A1 for a conveyor.
  • + location: where it is, for example +CAB1 for cabinet 1.
  • - product: the device itself, for example -K3 for a relay or -M1 for a motor.

EPLAN’s help gives the example =AP+ST1-F6: device F6 in function AP at location ST1 (EPLAN). A terminal or connection point follows a colon: -A1-X1:1 is connection point 1 of plug X1 on device A1, and -X2:14 is terminal 14 on terminal strip X2.

The letter after the minus sign says what kind of device it is (IEC 81346-2). K marks relays, Q contactors and circuit breakers that switch power, S push buttons and other hand-operated switches, B sensors, including limit and proximity switches, F fuses and other protection, M motors and X terminals. Older drawings often use K for contactors and S for limit switches, so check the legend. On a recent drawing, the -B12 from the HMI is a sensor, number 12.

US drawings use function letters instead. NFPA 79’s table includes CR for a control relay, M for a motor starter, PB for a push button, LS for a limit switch, OL for an overload relay, FU for a fuse and TB for a terminal block. US ladder drawings often start the tag with the number of the line the device sits on, so a control relay on line 115 is 115CR.

Terminal numbers follow their own logic. On an auxiliary contact the units digit gives the function, 1-2 for normally closed and 3-4 for normally open, and the tens digit counts the contacts. So 13-14 is the first contact, normally open, and 21-22 the second, normally closed (ABB). On an IEC contactor the coil terminals are A1 and A2 and the main contacts 1-2, 3-4 and 5-6 (Rockwell Automation). Plug-in interface relays, like the ones between many PLC outputs and their loads, usually have changeover contacts: 11 is the common, 12 the normally closed side and 14 the normally open side, then 21, 22 and 24 for the second contact.

Page and column references

A machine schematic can run to hundreds of pages, and a device often appears on several of them. On a European drawing the circuit runs top to bottom: the supply, such as +24 V or L1, runs across the top of the page, the return across the bottom, and each numbered column holds one current path. A cross-reference names the page and the column where the other part of the device is drawn. A US drawing points to a line number instead.

So a contact marked “/2.6” has its coil on page 2, column 6, and “.6” alone means column 6 on the same page. A reference into another part of a project carries its prefixes too, as in =AA1+BC1/2.5 (EPLAN). One trap: the page number is the page name in the title block, which is often not the page count in your PDF viewer.

The reference that saves you the most time at a cabinet is the contact image, drawn under or beside a relay or contactor coil. It lists every contact of that device with the page and column where each one is used (EPLAN), and each contact points back to its coil. On US drawings a note beside each coil lists the lines where its contacts are.

One contactor in two places: following -Q3 through the schematic
0123456789 +24 V 0 V Q8.0 -A1 -Q3 A1 A2 1-2/15.2 3-4/15.2 5-6/15.2 13-14/12.8 -Q3 /12.3 13 14 I4.0 -A2 Control, conveyor 3 Page 12 0123456789 L1 L2 L3 -Q3 /12.3 -X3 M 3~ -M3 Power, conveyor 3 motor Page 15

The coil of contactor -Q3 is on page 12, column 3. The contact image beside it lists every contact the coil switches and where each one is drawn, written as /page.column.

/15.2 means page 15, column 2. There the three main contacts switch the motor -M3, and their own reference, /12.3, points back to the coil.

Contact 13-14 is an auxiliary contact on the same page, column 8. When the contactor pulls in, it closes and tells the PLC on input I4.0.

An illustration, with letters and contact numbers as commonly used on IEC drawings. Motor protection, the protective earth and the main contact numbers are left out, and the page and column numbers are made up.

A wire that continues on another page ends in an interruption point, a small arrow labeled with the potential or signal name (EPLAN). In a PDF exported from EPLAN the references are links by default, so clicking a contact jumps to its coil (EPLAN). On a tablet at the machine, that alone is worth asking your machine builder for.

Wire numbers and colors

NFPA 79 requires conductors to be “identified at each termination by number, letter, color (either solid or with one or more stripes), or a combination thereof”, matching the documentation, so a wire found loose in the cabinet can be traced back to its circuit. The colors depend on the standard the machine was built to:

  • NFPA 79 (US, 2024 edition): black for AC and DC power, red for AC control, blue for DC control, green (with or without yellow stripes) for the equipment ground, and white or gray for a grounded AC conductor. Orange marks AC conductors that “remain energized when the main supply circuit disconnecting means is in the off position”, and orange with a blue stripe marks such DC conductors. White with a blue stripe marks a grounded DC conductor, such as the 0 V of a grounded 24 V DC supply, and white with an orange stripe a grounded conductor that stays live with the disconnect off.
  • IEC 60204-1 (Europe): black for AC and DC power, red for AC control, blue for DC control and orange for circuits that stay live (summary of clause 13). The protective conductor is green-and-yellow and the neutral blue, often a lighter shade than DC control wiring. Plenty of European cabinets don’t follow this code.

Orange wiring stays live with the main disconnect off, and NFPA 79 requires a sign at the disconnect saying so. Other parts stay live too: the incoming terminals of the disconnect itself, and any circuit fed from another machine or supply. Older US machines may use yellow for these circuits, and the standard allows exceptions, such as the internal wiring of devices bought prewired. Treat colors as a first hint, then confirm against the drawing and measure.

PLC input and output pages

A PLC page shows one input or output card with its channels in a row, each channel’s address, and the device wired to it, usually through a terminal. A Siemens address such as I0.0 reads as input byte 0, bit 0 (Siemens), and a Rockwell one such as Local:2:I.Data.3 as input bit 3 of the module in slot 2 of the local chassis (Rockwell Automation). Drawings from German builders often write Siemens addresses with the German letters, E0.0 for input I0.0 and A0.0 for output Q0.0.

The address is the bridge between the drawing and the program. The tag name in the program can differ from the device tag on the drawing, for example when the program was written before the wiring diagrams existed, and then the address is what connects the two. Our PLC troubleshooting guide picks up from there, on the program side.

How to read a schematic, in order

  1. Title block and revision: check that you have the current drawing for this machine.
  2. Legend and notes: learn the symbols and the tag system.
  3. Sheet index: find the pages for the part of the machine that failed.
  4. Power: find where its supply comes from, and the fuses or breakers on the way. Note any orange wiring.
  5. The circuit: read it from one rail to the other, device by device, remembering contacts are drawn de-energized.
  6. References: for each coil, use its contact image to find every contact it operates, and follow interruption points to other pages.
  7. PLC pages: note each address and find it in the program.
  8. Terminals and cables: find where the circuit leaves the cabinet and where it arrives in the field. For -B12, that’s the terminal, the cable and finally the sensor on the infeed.

Electrical troubleshooting with the schematic

The drawing comes before any measurement. NFPA 70E starts making equipment safe to work on by finding every source of supply, including from “applicable up-to-date drawings, diagrams, and identification tags”. OSHA adds that push buttons, selector switches and interlocks may not be used as the only means of de-energizing equipment, and that a qualified person must test that the parts are dead, including for voltage fed back from another source (OSHA 1910.333). Follow your plant’s lockout procedure. Stored energy counts too: a drive’s DC bus capacitors stay charged after the supply is off, so wait the time on the drive’s label and measure the DC bus before you touch it (more in VFD troubleshooting).

For proving dead, the UK’s HSE recommends a proper voltage detector, checked before and after use, and advises against multimeters, which can be set to the wrong function, and against non-contact volt sticks (HSE). In Europe, EN 50110-1 sums the work up as five rules: disconnect, secure against reconnection, verify that the installation is dead, earth and short-circuit, and cover or fence off nearby live parts (DEHN).

Then work from the symptom:

  • Start at the symptom. A contactor that doesn’t pull in, a PLC input that stays off, a lamp that doesn’t light. Find that device on the drawing.
  • Follow the circuit back to its supply. Every contact, fuse and terminal on the way is a point where the circuit can be open.
  • Measure voltage with the power on. Across each part of a series circuit with one open point, the good parts read close to zero volts and the open point reads the full supply voltage (FAA). Measured from the 0 V or neutral rail to each terminal in turn, the supply voltage is there up to the open point and gone after it. If A1 of a coil reads the supply voltage and the coil still doesn’t pull in, measure at A2: voltage there points to an open return to 0 V, and no voltage points to the coil. Live measurement is energized work, for qualified people with the protective equipment your plant’s procedure requires.
  • Measure resistance only with the power off and the part isolated from the rest of the circuit.
  • Halve the search. Measuring in the middle of a long chain tells you which half holds the fault, and repeating it narrows the search quickly.
  • Use the contact image. A relay that doesn’t switch affects every circuit its contacts appear in, and the contact image lists them all.

Where Edmund fits

The schematic tells you where a signal goes, but finding the right page during a stop still takes time, especially on a machine with hundreds of pages, and that time goes straight into your MTTR. Edmund reads your electrical drawings from EPLAN, CAD and AutoCAD PDF exports together with the PLC programs, so a tag like -B12 resolves to the cabinet, the terminal row and the terminal position, with the page it came from. If you’ve wondered whether a general chatbot can do the same, we compared them in Edmund vs ChatGPT for machine troubleshooting. And if you’d like to see it on your own drawings, send us a fault.

Frequently asked questions

How do you read an electrical schematic as a beginner?

Start with the legend and the title block, then follow one simple circuit, such as a push button switching a relay, from one rail to the other. Once that’s clear, use the relay’s contact image to find the pages where its contacts are drawn.

What is the difference between a schematic and a wiring diagram?

A schematic shows how a circuit works, laid out for tracing. A wiring diagram shows the physical connections: which wire goes to which terminal, roughly where the parts are.

How do you read a wiring diagram?

Find each device by its tag, then follow each wire by its number from terminal to terminal. The terminal diagram shows which wire lands on which terminal of a strip, and the schematic shows what the circuit does.

What do the numbers like /15.2 on a schematic mean?

They’re page and column references: /15.2 means page 15, column 2. Under a coil they show where its contacts are drawn, and next to a contact they point back to the coil.

What does -K mean on an electrical schematic?

In an IEC-style tag, the minus sign marks the device itself, and the letter after it is its class. K is the class for relays, so -K3 is relay 3. On a project divided by function or location, the tag is only unique with its prefixes: =A1-K3 and =A2-K3 are different relays.

Why are contacts drawn open on a schematic when the machine is running?

Schematics show every contact in its de-energized, resting state unless a symbol or note says otherwise. Whether a contact is open or closed on the running machine depends on whether its coil is energized.